CD Start Page | DATA ACQUISITION ONLINE Page | DATA ACQUISITION PRODUCTS Page |
The MCR-F Universal Frequency transducer converts any type of industrial frequency signal input range to standard analog process signals. Devices such as proximity sensors and magnetic speed switches can be utilized as frequency input devices.
The MCR-F Universal Frequency transducer family includes isolated and nonisolated versions. Each Model must be specified for either current or voltage signal outputs. The voltage and current output modules are signal (jumper) selectable. Voltage output module signal outputs are either 0-5 V dc or 0-10 V dc. Current modules are selectable for either 0-20 mA or 4-20 mA signal outputs.
The optional isolation of the MCR-F Universal Frequency module is achieved by use of a dc/dc converter on the 24 Vdc input circuit. Isolation of the input signal/output signals is accomplished by optical isolators. A maximum frequency range of 0-100 kHz provides a broad band of conversion application possibilities.
All adjustments are located behind a side door cover. Easy to follow setup and wiring instructions are located on the modules's 3-sided instruction labeling.
Internal calibration reference frequencies are jumper selectable for module field calibration. A wide ±20% zero/span adjustment provides excellent output resolution. All MCR-F Universal Frequency modules snap onto standard flat DIN-rail.
MODULE ISOLATION
Isolation will eliminate measurement errors due to ground loops and input signal noise. The dc/dc isolation converter is located on the incoming module power circuit. this effectively isolates the module's incoming 24 V dc power from the input/output signal circuits. Optical isolation is accomplished by the use of opto couplers placed across the frequency rotation circuits and the four input circuits.
NPN/PNP OPEN COLLECTOR INPUT
DRY CONTACT INPUT
The MCR-F Universal Frequency module produces a 1.25 mA current sensing circuit. At 1.25 mA dirty or oxidized contacts can still be monitored for open or closed status.
FREQUENCY
The minimum pulse width is 1µs. Voltage signal levels can range from 1 Vdc to 40 Vdc.
NAMUR SENSOR INPUT
OUTPUT SAMPLING/CONVERSION TIME
Slower frequencies require a long sampling/averaging period which produce stable analog outputs.
OUTPUT SAMPLING/CONVERSION TIME
VIEW an Adobe Acrobat pdf file for more product info (requires Acrobat Reader).
|
|